General specifications | |
---|---|
Switching function | Normally open (NO) |
Output type | NAMUR with safety function |
Rated operating distance | 3 mm |
Installation | flush in mild steel |
Assured operating distance | 0 ... 2.4 mm |
Actual operating distance | 2.7 ... 3.3 mm typ. |
Reduction factor rAl | 1 |
Reduction factor rCu | 1 |
Reduction factor r304 | 0 |
Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation. |
Output type | 2-wire |
Nominal ratings | |
Nominal voltage | 8.2 V |
Switching frequency | 0 ... 200 Hz |
Current consumption | |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 3 |
MTTFd | 10660 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives | |
Standard conformity | |
Approvals and certificates | |
EAC conformity | TRCU 012/2011 |
FM approval | |
UL approval | cULus Listed, General Purpose |
CCC approval | CCC approval / marking not required for products rated ?36 V |
Ambient conditions | |
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Mechanical specifications | |
Connection type | cable silicone , 5 m |
Core cross-section | 0.75 mm2 |
Housing material | Crastin (PBTB), black |
Sensing face | Crastin (PBTB), black |
Degree of protection | IP68 |
Cable | |
Note | only for non-ferrous metal |
Data for application in connection with hazardous areas | |
Equipment protection level | Ga , Gb , Gc (ic) , Gc (nA) , Da , Dc , Mb |
Equipment protection level Ga | |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
Effective internal capacitance | max. 70 nF A cable length of 10 m is considered. |
Effective internal inductance | max. 200 µH A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. |
Equipment protection level Gb | |
Type of protection | intrinsic safety |
CE marking | [*PD-Z02585A*] |
Certificates | |
Effective internal capacitance | max. 70 nF A cable length of 10 m is considered. |
Effective internal inductance | max. 200 µH A cable length of 10 m is considered. |
Maximum permissible ambient temperature | Also observe the maximum permissible ambient temperature stat |